Why is the earthing system relevant to the selection of your Surge Protection Device?

Posted on: November 25th 2026    •    Posted in: Product News

To answer this question, we need to understand how an SPD functions: 

If you have ever looked at an SPD and wondered what is actually happening inside the housing are not alone. 

There is a lot of confusion around how SPDs operate in the real world. Here is a straightforward breakdown of what goes on inside the unit, why they don’t just blow up after a single surge, and how to make sure you are fitting the right type for the installation. 

Think of an SPD like an overflow pipe on a sink or water tank. Rather than blocking or absorbing a power surge, it simply gives excess voltage a safe escape route to earth before it can reach (and damage) sensitive downstream equipment. 

Unlike a fuse or an MCB, which trips and cuts power to the circuit completely, an SPD stays connected. When a transient overvoltage hits, the SPD opens up a controlled path to earth. The moment the surge passes, it resets automatically and normal operation carries on as if nothing happened. 

Busting the biggest SPD myth: Many people assume SPDs are “one-use” devices that sacrifice themselves during a single surge. In reality, minor overvoltages happen on electrical systems all the time. If an SPD burned out after just one spike, it would offer very little practical protection.  

An SPD doesn’t cut the power—it diverts the excess voltage. 

Inside most standard SPDs, the main working component is a Metal Oxide Varistor (MOV). You can think of an MOV as a voltage-sensitive gatekeeper: 

  • During normal operation: Its electrical resistance is extremely high, so it sits quietly in the background without interfering with the supply. 
  • When a surge hits: If the voltage spikes above a set threshold (typically around 275V on a standard UK single-phase supply), the MOV’s resistance drops almost instantly. This creates a low-resistance path that channels the dangerous excess energy safely to earth. 
  • Once the surge clears: As soon as the voltage drops back to normal levels, the MOV’s resistance shoots back up, resetting the device for the next event. 

Every time an MOV clamps down on an overvoltage and over time it gradually wears down. As an MOV degrades, it can allow tiny amounts of current to leak to earth. This is completely normal. 

Eventually, when the MOV reaches the end of its working life and can no longer regulate its resistance safely, an internal thermal disconnector isolates the SPD from the supply. The indication on the front of the unit will then change, for example devices from our 360 Range will have a green LED that is illuminated when it is functional and that LED changes to red to let you know it is time for a replacement. 

Why Earthing Matters: TN vs. TT Systems 

When specifying or installing an SPD, understanding the site’s earthing arrangement is critical—because that tiny amount of end-of-life earth leakage behaves very differently depending on how the installation is earthed. 

  • TN Systems (TN-S and TN-C-S / PME): In most standard UK urban installations, the earth path goes straight back to the supply transformer. Minor leakage from an aging MOV won’t cause any operational issues. 
  • TT Systems: Common in rural areas, outbuildings, or EV/temporary setups, a TT system relies on a local earth rod rather than a direct connection to the supplier’s earth. Because fault loop impedances are higher, TT installations rely on sensitive upstream RCDs for fault protection—meaning even small amounts of earth leakage from an SPD can cause frustrating nuisance tripping. 

To stop nuisance tripping on TT systems, manufacturers pair the MOV with a Gas Discharge Tube (GDT). Wired in series with the MOV, the GDT acts as a barrier that completely blocks low-level leakage current under normal conditions, only conducting when a genuine high-voltage surge occurs. 

While a standard MOV-only SPD isn’t suitable for a TT system, an SPD with a GDT (rated for TT systems) can be safely installed on any earthing arrangement (TN-S, TN-C-S, or TT). 

Decoding the Jargon: CT1 vs. CT2 

If you check BS 7671, you will see these two internal configurations referred to as Connection Type 1 (CT1) and Connection Type 2 (CT2):  

Unless your go-to SPD is already a universal CT2 model rated for TT systems as standard, so can be used for all earthing systems, this needs to be considered when selecting the SPD. 

If you simply want one universal device on the van that covers every job without worrying about nuisance RCD trips—make sure you are fitting a CT2 device, such as our 360 Range of SPDs!